Test Report of Rolliflex Brand PVC INSULATED UNSHEATHED/SHEATHED ELECTRIC WIRES & CABLES Confirming to IS:694:1990 with Copper conductors upto and including 1100 Volts Grade. TC No.:
Control Unit No.:
Cable Size & Type:
Description of Test             Specified Values
Colour of Sheath              
Overall diameter in 'mm'             Max:
Colour of cores              
Outer Sheath Thickness in 'mm' Avg.             Avg:
Min.             Min:
Insulation Thickness in 'mm' Avg.             Avg:
Min.             Min:
Conductor Overall dia in 'mm'              
Resistance at 20*C in Ohms /Km             Max:
%Annealing of copper wire             Min:
Max. dia of Conductor wire 'mm'             Max:
Insulation Tensile Strength Before Ageing             Min: 12.5 N/mm^2
Elongation %Before Ageing             Min: 150%
Tensile Strength after Ageing             Min: 12.5 N/mm^2
Elongation % After Ageing             Min: 150%
% of Variation After Ageing Elongation %             Max: +/-20%
Tensile Stregth             Max: +/-20%
Heat shock test             No Signs of cracks
HD Test: Depth of Indentation             Max: 50%
Loss of mass in air mg/cm^2             Max: 2.00 mg/cm^2
Shrinkage test %             Max: 4.00% & No Cracks
Volume Resistivity in Ohm-Cm x10^13 27*C             Min: 1x10^13 ohm-cm
x10^10 70*C             Min: 1x10^10 ohm-cm
Sheath Tensile Strength Before Ageing             Min: 12.5 N/mm^2
Elongation % Before Ageing   Special Tests For C1 & C2 Category Cables Min: 150%
Tensile Strength After Ageing   Special Test Observed Specified Min: 12.5 N/mm^2
Elongation After Ageing %   Smoke Density Rating   Max: 60% Min: 150%
Heat Shock Test   Limiting Oxygen Index   Min: 29% No Signs of cracks
HD Test: Depth of Indentation   Temperature Index   Min: 250*C Max: 50%
Loss of mass in air oven   HCL Gas Emission   Max: 20% Max: 2.00 mg/cm^2
Shrinkage test %             Max: 4.00% & No Cracks
Flame Test Unaffected Length from Lower edge of Top Camp in 'mm'             Min: 50 mm
Burning time after Removal of Flame             Max: 60 seconds
High Voltage 3 K VAC - 5 minutes at Ambient             Voltage shall withstood
Water mmersion AC-6Kv for 5 mins             24 hrs Immersion at 60*C
DC-1.2Kv For 240 Hrs             240 hrs immersion at 60*C